|
|
2006 International Energy Conservation Code |
Built Green® Colorado
2007 Built Green Checklist
Tier I[1] |
2006 ENERGY STAR
National Performance Path
Requirements |
2006 ENERGY STAR
National Builder Option Package (BOP) |
USGBC LEED for Homes
V1.9
(in pilot phase until June 07) |
|
Minimum Energy Requirement |
If Section 404, Simulated Performance Alternative, used for compliance Performance a RESNET accredited HERS rating with HERS Index Score ≤ 100
Prescriptive Path follows Table 402.1.1. |
Builders are required to choose one of the three methods (items #1, #2 or #3 below) of meeting the Energy Efficiency Minimum Requirement. Note that item #2 requires a higher level of testing than required by the program’s random verification process, and that item #3, energy star®, exceeds the “minimum” requirement; hence option #2 and #3 are awarded points while option #1 is not.
Using REScheck, REM-Rate or EnergyGauge software, verify that calculated performance is projected to exceed requirements of Chapter 4, Section 404 (Performance) of the IECC 2006 by at least 15%; in addition, comply with Built Green Checklist Appendix A (requirements of Chapters 3 and 4 of the IECC 2006 not addressed by REScheck, REMRate or EnergyGauge).
OR
RESNET-accredited HERS Rating of 85 points or less when using the expanded HERS “INDEX” score based on the 2006 HERS Reference Home. Homes must commit to this compliance method and be tested on a 15% or higher basis in order to take these points
OR
House meets energy star® criteria by either the Prescriptive or Performance paths as outlined by the US Environmental Protection Agency (Cannot combine with item #2 “RESNET-accredited”)
|
RESNET-accredited HERS Rating with HERS Index Score ≤ 85 when using the new “INDEX” HERS score with the reference house based on the IECC 2006.
|
A Builder Option Package (BOP) provides a set of construction specifications that enable a home to qualify for the ENERGY STAR label. Although using the BOP negates the need for a custom HERS rating, third-party verification that all BOP requirements have been met is still necessary.
|
RESNET-accredited HERS Rating with HERS Index Score ≤ 85 when using the new “INDEX” HERS score with the reference house based on the IECC 2004 Supplement.
|
|
Space Cooling |
Must meet Federal Minimum standard. Currently SEER13 for split residential system.
Section 403.6 (Mandatory) Equipment Sizing. Heating and cooling equipment shall be sized in accordance with Section M1403.3 of the IRC.
Section 403.5 (Mandatory) Mechanical Ventilation. (if present) must have automatic or gravity dampers. |
Builder has flexibility with the selection of energy-efficiency measures as they pertain to space cooling equipment, with points for higher performance achievable through a variety of available options. Builder, at a minimum, must meet code.
See Category X of the BUILT GREEN® CHECKLIST for available options.
*Note that one option from Category “X: Energy Efficiency: Mechanical Heating & Cooling Systems” is required.
|
Builder has flexibility with the selection of energy-efficiency measures as they pertain to space cooling equipment. Builder, at a minimum, must meet code.
All cooling equipment, ENERGY STAR or otherwise, shall be sized according to the latest editions of ACCA Manuals J and S, ASHRAE 200l Handbook of Fundamentals, or an equivalent computation procedure.
Maximum oversizing limit for air conditioners and heat pumps is 15% (with the exception of heat pumps in Climate Zones 5-8, where the maximum oversizing limit is 25%).
Indoor and outdoor coils shall be matched in accordance with ARI standards. |
≥ 13 SEER OR ENERGY STAR qualifying heat pump
All cooling equipment, ENERGY STAR or otherwise, shall be sized according to the latest editions of ACCA Manuals J and S, ASHRAE 200l Handbook of Fundamentals or an equivalent computation procedure. Maximum oversizing limit for air conditioners and heat pumps is 15% (with the exception of heat pumps in Climate Zones 5-8, where the maximum oversizing limit is 25%).
Indoor and outdoor coils shall be matched in accordance with ARI standards. |
Meets ENERGY STAR HVAC requirements with refrigerant charge test.
Equipment sizing using ACCA Manual J, 8th Edition. |
|
Space Heating |
Right-Sized:
Gas-fired furnace < 225,000 Btu/h = 78% AFUE
OR
Air-cooled heat pumps, Heating mode <65,000 Btu/h cooling capacity=6.6 – 6.8 HSPF
OR
Gas-fired or oil-fired steam and hot-water boilers < 300,000 Btu/h=80% AFUE
HVAC Piping Insulation
Section 403.6 (Mandatory) Equipment Sizing. Heating and cooling equipment shall be sized in accordance with Section M1403.3 of the IRC.
Section 403.5 (Mandatory) Mechanical Ventilation. (if present) must have automatic or gravity dampers.
|
Builder has flexibility with the selection of energy-efficiency measures as they pertain to the selection of space heating equipment, with points for higher performance achieved through a variety of available options. Builder, at a minimum, must meet code.
See Category X of the BUILT GREEN® CHECKLIST for available options.
*One option from Category “X: Energy Efficiency: Mechanical Heating & Cooling Systems” is required. Category IX provides points for low-energy cooling.
|
Builder has flexibility with the selection of energy-efficiency measures as they pertain to the selection of space heating equipment. Builder, at a minimum, must meet code. |
ENERGY STAR qualified gas furnace (≥90% AFUE)
OR
ENERGY STAR qualified heat pump
OR
ENERGY STAR qualified boiler
OR
85% AFUE oil furnace |
Meets ENERGY STAR HVAC requirements with Manual J. |
|
Thermostat |
Required (capable of being set locally or remotely by adjustment or selection of sensors).
|
Flexibility, with points for higher performance achieved through a variety of available options, with code minimum.
See Category X of the BUILT GREEN® CHECKLIST for available options.
*One option from Category “X: Energy Efficiency: Mechanical Heating & Cooling Systems” is required.
|
Builder has flexibility with the selection of thermostats, with code minimum.
|
ENERGY STAR qualified thermostat
(except for zones with radiant heat) |
|
|
Duct Distribution Systems |
Supply and return ducts shall be insulated to R-8. Ducts in floor trusses (interfacing unconditioned space) shall be insulated to a minimum R-6. Ducts in conditioned space not required to be insulated.
Sealing required. UL 181A or UL 181B tapes (flex ducts only) and mastics.
Balancing required.
Ducts, air handlers, filter boxes, and, if used, building cavities shall be sealed.
|
Flexibility, with points for higher performance achieved through a variety of available options, with code minimum.
See Category XI of the BUILT GREEN® CHECKLIST for available options.
*One option from Category “XI: Energy Efficiency: HVAC Distribution Systems” is required.
|
Ducts must be sealed and tested to be = 6 cfm to outdoors 100 sf of conditioned floor area, as determined and documented by RESNET—certified rater using a RESNET-approved testing protocol. < P>
Duct leakage testing can be waived if all ducts and air handling equipment are located in conditioned space AND the envelope leakage has been tested to be ≤ 3 ACH50 OR ≤0.25 CFM50 per s.f. of the building envelope. |
Ducts must be sealed and tested to be ≤ 4 cfm to outdoors/100 s.f. of conditioned floor area, as determined and documented by a RESNET-certified rater using a RESNET-approved testing protocol.
Duct leakage testing can be waived if all ducts and air handling equipment are located in conditioned space AND the envelope leakage has been tested to be ≤ 3 ACH50 OR ≤0.25 CFM50 per s.f. of the building envelope. Minimum R-6 on ducts in unconditioned spaces. |
Third-party duct leakage tested ≤ 4.0 CFM 25/100 s.f. to the outside. Additional points available for greater system tightness levels.
|
|
Envelope |
From Table 402.1.1 for Climate Zone 5
· Ceiling R-38
· Wall R-19 (or 13+ 5) or 13+ 2 with structural sheathing
· Floor R-30 (or insulation sufficient to fill the cavity, R-19 minimum)
· Basement wall R-10/13
· Slab perimeter and depth, R-10, 2 ft
· Crawl R-10/13
Flexibility of envelope requirements if Section 404 is used as the compliance path. Also 13+5, 13+2 structural sheathing not required in Section 404.
Ceiling R-30, 500 ft2, if ceiling cavity cannot support R-38.
|
Flexibility, with points for higher performance achieved through a variety of available options, with code minimum.
See Category VII of the BUILT GREEN® CHECKLIST for available options.
|
Flexibility, with the ability to achieve higher aggregate energy savings through a variety of energy-efficiency measures, with code minimum.
|
Insulation levels must meet or exceed Sections N1102.1and N1102.2 of the 2004 IRC (as they apply to Climate Zone 5 only):
· Ceiling R-38
· Wall R-19 or R-13+5
· Floor R-30
· Basement wall R-10/13
· Slab perimeter and depth R-10, 2 ft.
· Crawlspace R-10/13
Insulation shall be inspected to be Grade I installation as defined in the RESNET standards by a RESNET-certified rater. |
Third-party envelope air leakage tested at ≤ 7.0 CFM 50 (CZ1-5). |
|
Air Sealing |
Caulking/Sealing:
· Around tubs and showers
· Attic and crawlspace panels
· Plumbing and electrical penetrations
· Between duct boot and subfloor
· Around perimeter joist between floors
· Around chimneys and flue chases that pass through the attic
· Exterior penetrations |
Flexibility, with points for higher performance achieved through a variety of available options, with code minimum.
See Category VII of the BUILT GREEN® CHECKLIST for available options.
|
Compliance with Thermal Bypass Inspection Checklist. |
Compliance with the Thermal Bypass Inspection Checklist. |
Compliance with the Thermal Bypass Inspection Checklist. |
|
Windows |
Maximum U-factor ≤ 0.35. |
Flexibility, with points for higher performance achieved through a variety of available options, with code minimum.
See Category VIII of the BUILT GREEN® CHECKLIST for available options.
|
Flexibility, with the ability to achieve higher aggregate energy savings, with code minimum. |
ENERGY STAR qualified windows or better (U-factor ≤ 0.35). For homes with a WFA > 18%, an improved window U-value is required.
|
Meets ENERGY STAR for windows. |
|
Water Heater |
Gas: Any Gas >/= 0.62 EF minus 0.0019V (storage volume in gallons as specified by the manufacturer).
Meets minimum requirements for the current National Energy Conservation Act (NAECA) of 1987.
|
Flexibility, with points for higher performance achieved through a variety of available options, with code minimum.
See Category XIV of the BUILT GREEN® CHECKLIST for available options. |
Flexibility, with the ability to achieve higher aggregate energy savings, with code minimum. |
Gas: 0.61 EF (40 gal), 0.57 EF (60 gal), 0.53 EF (80 gal)
Electric: 0.93 EF (40 gal), 0.92 EF (50 gal), 0.89 (80 gal)[2]
|
Flexibility, with points awarded for improved hot water distribution systems and improved hot water heating equipment. |
|
Lighting & Appliances |
|
Flexibility, with points for higher performance achieved through a variety of available options, with code minimum.
See Categories XV and XVI of the BUILT GREEN® CHECKLIST for available options.
*One option from Category “SVI: Energy Efficiency: Lighting” is required.
|
See below. |
5 or more ENERGY STAR qualified appliances, light fixtures, ceiling fans equipped with lighting fixtures, and/or ventilation fans. |
3 ENERGY STAR light fixtures or ENERGY STAR CFLs |
|
ENERGY STAR Products |
|
Builder has flexibility with the selection of ENERGY STAR labeled products. Use of ENERGY STAR labeled products is awarded points. |
Include at least 1 ENERGY STAR Qualified Product Category:
Heating or cooling equipment:
OR
Windows;
OR
Five or more ENERGY STAR qualified lights fixtures, appliances, ceiling fans equipped with lighting fixtures, or ventilation fans. No more than 20% of sockets can use CFLs to increase HERS Index Score to qualify as ENERGY STAR. |
|
Builder has flexibility with the selection of ENERGY STAR labeled products. Use of ENERGY STAR labeled products is awarded points. |